SINE WAVE STATIC UPS & INVERTER

Overview

Salient Features & Comparison with Other available Brands

  • State of Art MOSFET/IGBT based PWM technology to increase Crest Factor Yes Yes
  • Fast Changeover ensuring reliable Compatibility with Computers No Yes
  • Electronic changeover, hence much better reliability other are using relay for changeover whereas we are using SCR No Yes
  • Selector Switch for Normal/UPS No Yes
  • TDR (Time Delay Relay), especially for AC compressor based applications partly (some brands have some does not have) Yes Yes
  • LCD Display options Yes Yes
  • Surge Load Capacity upto 300% No Yes
  • DSP based which results proper control over voltage and current No Yes
Sr No. PARAMETERS/CHECKS 2.5KVA/48V 3.5KVA/48V 5KVA/48V 5KVA/96V 7.5KVA/120V 10KVA/120V
(A) INVERTER MODE
1 No Load Battery Current (Maximum) 1.1±0.4A 1.5±0.4A 2.2±0.4A 1.1±0.4A 1.5±0.4A 1.5±0.4A
2 Max. O/P No Load Voltage 220 ±5V 220 ±5V 220 ± 5V 220 ±5V 230±5V 230±5V
3 Max. O/P Full Load Voltage 220 ±7% 220 ±7% 220 ±7% 220 ±7% 230±10% 230±10%
4 OutPut Frequency (Inverter Mode) 50.0 ± 1.0 Hz 50.0 ± 1.0 Hz 50.0 ± 1.0 Hz 50.0 ± 1.0 Hz 50.0 ± 0.5Hz 50.0 ± 0.5Hz
5 Full Load Battery Current (Maximum) 46±2A 63A±2A 104±2A 46±2A 63±2A 77±2A
6 Full Load O/P Current 8.5±0.5A 12.0±0.5A 17±0.5A 17±0.5A 27 ±0.5A 34 ±0.5A
7 Overload Retry 6 Times 6 Times 6 Times 6 Times 6 Times 6 Times
8 OutPut Sine Wave (Inverter) Should be OK Should be OK Should be OK Should be OK Should be OK Should be OK
(B) MAINS MODE
1 OutPut Sine Wave (Mains) Should be OK Should be OK Should be OK Should be OK Should be OK Should be OK
2 Mains Low Cut 100±10V 100±10V 100±10V 125±10V 125±10V 125±10V
3 Recovery 110±10V 110±10V 110±10V 135±10V 135±10V 135±10V
4 Mains High Cut 280±10V 280±10V 280±10V 280±10V 280±10V 280±10V
5 Recovery 275±10V 275±10V 275±10V 275±10V 275±10V 275±10V
6 Change Over Time (Mains to Inverter) <50 ms <50 ms <50 ms <50 ms <50 ms <50 ms
7 Change Over Time (Inverter to Mains) <10 ms <10 ms <10 ms <10 ms <10 ms <10 ms
8 Batt Low Buzzer (V/Batt) 10.8V ±0.2V 10.8V ±0.2V 10.8V ±0.2V 10.8V ±0.2V 10.8V ±0.2V 10.8V ±0.2V
9 Batt Low Cut (V/Batt) 10.5V ±0.2V 10.5V ±0.2V 10.5V ±0.2V 10.5V ±0.2V 10.5V ±0.2V 10.5V ±0.2V
10 Batt Low Retry 4 Times 4 Times 4 Times 4 Times 4 Times 4 Times
11 Short Circuit, Retry OK, 1 Time OK, 1 Time OK, 1 Time OK, 1 Time OK, 1 Time OK, 1 Time
12 Permanent Short Circuit Protection Should be OK Should be OK Should be OK Should be OK Should be OK Should be OK
(C) UPS MODE
1 Mains Low Cut 180±10V 180±10V 180±10V 180±10V 180±10V 180±10V
2 Recovery 190±10V 190±10V 190±10V 190±10V 190±10V 190±10V
3 Mains High Cut 260±10V 260±10V 260±10V 260±10V 260±10V 260±10V
4 Recovery 255±10V 255±10V 255±10V 255±10V 255±10V 255±10V
5 Change Over Time (Mains to UPS) <=10 ms <=10 ms <=10 ms <=10 ms <=10 ms <=10 ms
6 Change Over Time (UPS to Mains) <10 ms <10 ms <10 ms <10 ms <10 ms <10 ms
(D) CHARGING MODE
1 Charging Current @ 220VAC @TUB 10/12 Amp. ± 1Amp 10/12 Amp. ± 1Amp 10/12 Amp. ± 1Amp 10/12 Amp. ± 1Amp 10/12 Amp. ± 1Amp 10/12 Amp. ± 1Amp
2 Boost Charging Voltage @TUB /Batt. 57.6V ± 0.2V 57.6V ± 0.2V 57.6V ± 0.2V 115.2V ± 0.2V 144V ± 0.2V 144V ± 0.2V
3 Float Charging Voltage @GEL /Batt. 54.8V ± 0.2V 54.8V ± 0.2V 54.8V ± 0.2V 109.6V ± 0.2V 137V ± 0.2V 137V ± 0.2V
(E) PROTECTIONS
1 Over Load Warning >46Amp. 6 Auto Retries >63Amp. 6 Auto Retries >104Amp. 6 Auto Retries >47Amp. 6 Auto Retries >64Amp. 6 Auto Retries >77Amp. 6 Auto Retries
2 Over Load Protection Shut Down after 6 Retries and show Protection Shut Down after 6 Retries and show Protection Shut Down after 6 Retries and show Protection Shut Down after 6 Retries and show Protection Shut Down after 6 Retries and show Protection Shut Down after 6 Retries and show Protection
3 Over Load Shut Down Reset Through PCU Switch & Mains Through PCU Switch & Mains Through PCU Switch & Mains Through PCU Switch & Mains Through PCU Switch & Mains Through PCU Switch & Mains
4 Battery Low Alarm per battery @12V 10.8V ± 0.2V 10.8V ± 0.2V 10.8V ± 0.2V 10.8V ± 0.2V 10.8V ± 0.2V 10.8V ± 0.2V
5 Battery Low Protection per battery @12V 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5V ± 0.2V 4 Auto Retries Shut Down after 4 Retries
6 Battery Low Shut Down Reset Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains
7 Over Temperature Alarm should be Ok should be Ok should be Ok should be Ok should be Ok should be Ok
8 Short Ckts (Mains Mode) Mains MCB Trip Mains MCB Trip Mains MCB Trip Mains MCB Trip Mains MCB Trip Mains MCB Trip
9 Short Ckts Protection (battery Mode) should be Ok should be Ok should be Ok should be Ok should be Ok should be Ok
10 Short Ckts Retry (battery Mode) One Retry One Retry One Retry One Retry One Retry One Retry
11 Short Ckt Reset Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains
12 Mains MCB Trip should be Ok should be Ok should be Ok should be Ok should be Ok should be Ok