SINE WAVE HOME UPS & INVERTER

Overview

Our products are the outcome of passion of a few young and enthusiastic technocrats. Since its inception the company has conquered new horizons and set new standards for the industry. Cutting-edge technology and international class of manufacturing facilities and total focus on quality and testing ensure that all our Inverters & UPS, give sustained trouble Zunax pioneered Pure Sine Wave technology in its inverters, UPS and power supplies. Our Sine Wave inverters output stable frequency and voltage, mimicking mains power supply, making it perfectly suitable to power expensive equipments, especially inductive loads that do not work well on square waves. Other products in markets deliver distorted output waveforms particularly on normally encountered loads like Compact Fluorescent Lamp (CFL), Tube Lights, Motors, Air Coolers, and Computers etc. This Distorted waveform is harmful for almost all the home appliances. Zunax, DSP Sinewave Home UPS & Inverter delivers quality output with reliable performance at a reasonable price. Zunax DSP based Sine Wave inverters & UPS are specialized in providing clean and stable power supply to all connected appliances and equipments.

Sr No. BATTERY MODE 650VA/12V 850VA/12V 1050VA/12V 1450VA/24V 2000VA/24V
1 Maximum No Load Current @ 12V DC <=2.2Amp. <=2.6Amp <=2.6Amp <=2.2Amp. <=2.2Amp
2 Output Voltage (No Load) @ 12 V DC 220V ±7V 220V ±7V 220V ±7V 220V ±7V 220V ±7V
3 Full Load Output Voltage @ 12 V DC 195V-220V 195V-220V 180V-220V 180V-220V 180V-220V
4 Output Frequency No Load-Full Load 50 Hz +/- 1 Hz 50 Hz +/- 1 Hz 50 Hz +/- 1 Hz 50 Hz +/- 1 Hz 50 Hz +/- 1 Hz
5 Full Load Battery Current 43 Amp. ± 2Amp 57Amp. ± 2Amp 63Amp. ± 2Amp 47Amp. ± 2Amp. 62Amp. ± 2Amp
6 No Load Current @ Switch Off <150 mA <150 mA <180 mA <150 mA <200 mA
7 Fan Run @ >50%Load & Temperature dependent Should be Ok Should be Ok Should be Ok Should be Ok Should be Ok
MAINS MODE
(A) UPS MODE
1 Low Cut Voltage 180±10V 180±10V 180±10V 180±10V 180±10V
2 Low Cut Recovery 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS
3 High Cut 260V ± 10V 260V ± 10V 260V ± 10V 260V ± 10V 260V ± 10V
4 High Cut Recovery 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS
5 Change Over Mains to UPS <=10ms <=10ms <=10ms <=10ms <=10ms
6 Change Over UPS to Mains <= 10ms <= 10ms <= 10ms <= 10ms <= 10ms
(B) NORMAL MODE
1 Low Cut Voltage 100V±10V 100V±10V 100V±10V 100V±10V 100V±10V
2 Low Cut Voltage Recovery 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS
3 High Cut 280V ± 10V 280V ± 10V 280V ± 10V 280V ± 10V 280V ± 10V
4 High Cut Recovery 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS 9V-12V HYSTERSIS
5 Change Over MAINS to INVERTER <=40ms <=40ms <=40ms <=40ms <=40ms
6 Change Over INVERTER to MAINS <= 10ms <= 10ms <= 10ms <= 10ms <= 10ms
(C) CHARGING MODE
1 Charging Current @ 220VAC 12/16 Amp. ± 1Amp. 12/16 Amp. ± 1Amp. 12/16 Amp. ± 1Amp. 12/16 Amp. ± 1Amp. 12/16 Amp. ± 1Amp.
2 Boost Voltage 14.4 ± 0.2 14.4 ± 0.3 14.4 ± 0.4 28.8 ± 0.2 28.8 ± 0.2
3 Float Voltage 13.7 ± 0.2 13.7 ± 0.3 13.7 ± 0.4 27.4 ± 0.2 27.4 ± 0.2
(D) PROTECTIONS
1 Over Load Protection 6 Auto Retries Shut Down after 6 Retries 7 Auto Retries Shut Down after 6 Retrie 8 Auto Retries Shut Down after 6 Retries 6 Auto Retries Shut Down after 6 Retries 6 Auto Retries Shut Down after 6 Retries
2 Over Load Shut Down Reset Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains
3 Battery Low Alarm 10.8 V ± 0.2V 10.8 V ± 0.2V 10.8 V ± 0.2V 21.6V ± 0.2V 21.6V ± 0.2V
4 Battery Low Protection 10.5 V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5 V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 10.5 V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 21.0V ± 0.2V 4 Auto Retries Shut Down after 4 Retries 21.0V ± 0.2V 4 Auto Retries Shut Down after 4 Retries
5 Battery Low Shut Down Reset Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains Through On/Off Switch & Mains
6 Over Temperature Alarm should be Ok should be Ok should be Ok should be Ok should be Ok
7 Short Ckts (Mains Mode) Main Fuse Blow Main Fuse Blow Main Fuse Blow Main Fuse Blow Main Fuse Blow
8 Short Ckts Protection (battery Mode should be Ok should be Ok should be Ok should be Ok should be Ok
9 Short Ckts Retry No No No No No
10 Short Ckt Reset Through On/Off Switch Through On/Off Switch Through On/Off Switch/td> Through On/Off Switch Through On/Off
11 Mains Fuse Trip should be Ok should be Ok should be Ok should be Ok should be Ok